ENGINEERED SYSTEM
Eckoshield® - 227ea
(HFC227ea Fire Suppression System)
Fire and Security Techniques Eckoshield® 227ea engineered fire suppression system is highly recommended for larger areas that may have multiple risks, and covers a wide array of application spaces.
Engineered Fire Suppression Systems
Eckoshield® - 227ea
Fire and Security Techniques Eckoshield® 227ea engineered fire suppression solution is highly recommended for larger areas that may have multiple risks, and covers a wide array of application spaces. As engineered fire suppression systems differ to that of modular pre-engineered systems, the Eckoshield® 227ea engineered system utilises distribution pipework in order to deliver the gas to the risk/s.
The benefit of using Eckoshield® 227ea is that extinguishment is less than 10 seconds and is safe for occupied spaces. Fire and Security Techniques is a specialised design application company with registered SAQCC designers and holds the BSI Kitemark™ for fire suppression system designs. We are always eager to take on new challenges and can provide you with all the necessary specifications and requirements whilst ensuring no detail is overlooked.
Engineered Systems
Extinguishing Method:
- Heat absorption
- Interrupts fire reaction
Engineered Systems
Valve Options:
- VG valve- 100-175lt
- DIN valve- 6-58lt
- EAV valve- 6-58lt
Valve Range | Valve Length | Valve Weight |
FFE Valve | 110mm | 1.2kg |
VERI GOOD valve | 200mm | 9.2kg |
Engineered Systems
Advantages Eckoshield® 227ea Clean Agent Gas
- Extinguishes in less than 10 seconds
- Leaves no residue
- Ideal for occupied spaces
- Electrically non-conductive
- Non-toxic
- Low environmental impact
Engineered Systems
Advantages Eckoshield® Engineered System
- Cost efficient
- Total flooding
- FST holds BSI Kitemark™ on fire system designs
- SAQCC registered designers
Engineered Systems
Cylinder Sizes
Cylinder capacity | Cylinder length C/W valve (mm) | Cylinder diameter (mm) | Cylinder diameter incl. bracket (mm) | Tare weight Incl. bracket not Incl. Valve (kg) | Minimum fill per cylinder (kg) | Max fill per cylinder (kg) |
6 lt | 460 | 200 | 260 | 8.7 | 3 | 6 |
10 lt | 590 | 200 | 260 | 10.9 | 5 | 11 |
15 lt skinny | 750 | 200 | 260 | 14.1 | 8 | 16 |
25 lt skinny | 1090 | 200 | 260 | 20.2 | 13 | 27 |
25 lt | 590 | 300 | 360 | 16.3 | 13 | 27 |
45 lt | 860 | 300 | 360 | 24.4 | 23 | 49 |
58 lt | 1100 | 300 | n/a | 26 | 29 | 63 |
100 lt | 960 | 460 | n/a | 62 | 50 | 110 |
150 lt | 1310 | 460 | n/a | 85 | 75 | 165 |
175 lt | 1470 | 460 | n/a | 87 | 87 | 192 |
Engineered Systems
Applications
- Critical Assets
- Data Processing Centres
- IT Systems/Software
- Telecommunications Equipment
- Library Collections
- Museum Collections
- Art Storage
- Original Document Storage
- Bank Vault Systems
- Generator And Turbine Enclosures