GAS CONTROL PANEL
3 Zone Combination Panel
(TS-AE-TC 3001) - Fire & Extinguishing Control
The TC3000 Extinguishing System not only detects fires like a regular alarm but also releases extinguishing agents, boasts advanced features like double-knock detection, and is ideal for protecting high-value business areas.
GAS CONTROL PANEL
3 Zone Combination Panel
R10 973,63
The TC3000 system detects a fire in the same manner as a fire alarm system. However, in addition to sounding alarms, it also controls the release of an extinguishing agent. The extinguishing agent can take many forms, from CO2 through to specialised gases such as the Stat-X® aerosol suppression range, which was developed solely for extinguishing purposes. The fire is extinguished when the agent reduces the oxygen density in the atmosphere around the fire.
The TC3000 is packed with unique features, including a large LCD graphical display and keypad. The control panel comes with three detection zones, a time & date-stamped log, advanced cause-and-effect, and extensive I/O. To avoid false discharges, the TC3001 can utilise coincidence detection or double-knock, requiring activation of a fire detector in two separate zones before activating a gas release.
Optional accessories for the system include networked Remote Status Panels, Hold or Abort pushbuttons, and Active EOL units. This makes the TC3000 one of the most advanced solutions available.
The TC3000 Extinguishing System is used primarily in areas of significant value or strategic importance to businesses, such as computer suites and telecom infrastructure. It provides a cost-effective solution to protect your workplace.
GAS CONTROL PANEL
Key Features
- EN 12094-1 Approved
- EN 54-2 & EN 54-4 Approved
- Full CPD Approval
- 3 Year warranty
- Alphanumeric keypad
- Logo programming software
- Real-time clock, time & date - stamped event log
- Software extraction tool for downloading, configuration and event logs
- Countdown timer
GAS CONTROL PANEL
Features
- User-friendly graphical LCD display providing clearer status
- Information and programming routines
- Multiple languages
- Passcode replaces physical key for Level 2 access (optional keyswitch can be fitted if key is preferred)
- Company logo can be displayed on LCD during normal conditions.
- RS485 for Remote Status Indicators.
GAS CONTROL PANEL
Specifications
- Base Technology
- Display
- LED Indicators
- Controls
- Number of Conventional Detection Zones
- Flooding / Extinguishing Zones
- On Board Sounder circuits
- On Board Relays
- Auxiliary Supply
- Programmable Outputs
- Switch Inputs
- Countdown Timer
- Mains Supply
- Battery Capacity
- Charger Current
- USB ports
- Event Log
- Enclosure / Colour
- Cable Entry
- Size H x W x D mm
- Flash-based processor (Real time clock with time stamped event log)
- Backlit 128 x 64 Graphical LCD
- Remote Status indicators are supported via RS485
- Alphanumeric Keypad, Navigation Keys & System Keys for Reset, Mute, Silence/ Resound & Sound Alarm
- 3x Conventional detection zones (incl. support for IS barrier)
- 1x Flooding / Extinguishing Zones (Support for both Solenoid and Metron type actuators)
- 3x 700mA, 21-28V DC
- 4x 1A, 30V DC Relay Outputs (Fire, Fault & 2 Programmable)
- 2x 400mA Aux Supply Outputs, 21-28V DC (1 Switched)
- 4x Programmable, 1x Manual Trigger (Support for 2 or 8 additional programmable outputs via Exp-002/8)
- 6x Release Related (Mode Select, Valve Monitor, Pressure Monitor, Hold, Abort & Flow)
- Large digit countdown timer
- 3A Universal switch mode PSU
- 24V, 7Ah
- 1A
- 1x USB port onboard for PC download
- 1,000 event time stamped event log
- Steel IP30 / Grey RAL7035
- 17 knockouts in the top, 13 knockouts in the back
- 330 x 400 x 95